SASO 2663:2014 - MEPS and labelling for air conditioners
The minimum energy performance standard MEPS value for the air conditioner in the scope of this standard shall be greater than or equal to the value of Energy Effeicency Ratio (EER), When calculating the cooling capacity at test conditions (T1) and test condition (T3) as follows:
Single package of Window type:
CC = 18000:
-From 2013 EER at test condition T1: 8.5 ; EER at test condition T3: 6.12
-From 2015 EER at test condition T1: 9.8 ; EER at test condition T3: 7.06
18000 < CC = 24000:
-From 2013 EER at test condition T1: 8.5 ; EER at test condition T3: 6.12
-From 2015 EER at test condition T1: 9.7 ; EER at test condition T3: 6.98
24000 < CC
-From 2013 EER at test condition T1: 8.5 ; EER at test condition T3: 6.12
-From 2015 EER at test condition T1: 8.5 ; EER at test condition T3: 6.12
Split type ducted and non-ducted using air-cooled condensers, heat pumps using air-cooled condensers
CC = 70000
-From 2013 EER at test condition T1: 9 ; EER at test condition T3: 6.84
-From 2015 EER at test condition T1: 11.5 ; EER at test condition T3: 8.28 CC, Cooling Capacity (CC) (Btu/h) at test condition T1.