Minimum Energy Performance Standards and Labelling for Air Conditioners with Cooling Capacity = 7.1kW
TESTING STANDARD
ISO 16358-1:2013
MS ISO 5151:2012
RATING AND TESTING CONDITION
CSPF for non-inverter type is calculated by multiplying EER tested at standard temperature condition by 1.062
CSPF = 1.062 x Tested EER
CSPF for inverter-type, the 50% load cooling capacity test will be used with the following tolerance
50% load = 100 % load capacity x 0.5 (tolerance ± 5.0 %), where 100% load capacity refers to measured cooling capacity during 100% load cooling capacity.
Testing conditions will be based on:
- climactic ambient T1, refer to MS ISO 5151
- Voltage 230V, 50Hz
STAR LABELLING (in CSPF, Wh/Wh)
The rated cooling capacity < 4.5kW
5-star: =5.30
4-star: 4.60 =CSPF<5.30
3-star: 3.30 = CSPF<4.60
2-star: 3.10 = CSPF<3.30
1-star: <3.10
4.5kW =Rated Cooling Capacity = 7.1kW
5-star: = 5.10
4-star: 4.00= CSPF<5.10
3-star: 3.10= CSPF<4.00
2-star: 2.90 = CSPF<3.10
1-star: <2.90
MINIMUM ENERGY PERFORMANCE STANDARDS (MEPS)
MEPS requirement is 2-stars, hence 3.10 Wh/Wh (for less than 4.5 kW) and 2.90 Wh/Wh (for less than 7.1kW)