Minimum Efficiency Standards for Variable Refrigerant Flow Multi-Split Air Conditioners and Heat Pumps
Each variable refrigerant flow air conditioner or heat pump manufactured on or after the compliance date listed below must meet the applicable minimum energy efficiency standard level(s) as detailed below.
VRF Multi-Split Air Conditioners (Air-Cooled)
<65,000 Btu/h - SEER 13.0 - Compliance date: June 16, 2008
=65,000 Btu/h and <135,000 Btu/h
No Heating or Electric Resistance Heating - EER 11.2 - Compliance date: January 1, 2010
All Other Types of Heating - EER 11.0 - Compliance date: January 1, 2010
=135,000 Btu/h and <240,000 Btu/h
No Heating or Electric Resistance Heating - EER 11.0 - Compliance date: January 1, 2010
All Other Types of Heating - EER 10.8 - Compliance date: January 1, 2010
=240,000 Btu/h and <760,000 Btu/h
No Heating or Electric Resistance Heating - EER 10.0 - Compliance date: January 1, 2010
All Other Types of Heating - EER 9.8 - Compliance date: January 1, 2010
VRF Multi-Split Heat Pumps (Air-Cooled)
<65,000 Btu/h - SEER 13.0 - HSPF 7.7 - Compliance date: June 16, 2008
=65,000 Btu/h and <135,000 Btu/h
No Heating or Electric Resistance Heating - EER 11.0 - COP 3.3 - Compliance date: January 1, 2010
All Other Types of Heating - EER 10.8 - COP 3.3 - Compliance date: January 1, 2010
=135,000 Btu/h and <240,000 Btu/h
No Heating or Electric Resistance Heating - EER 10.6 - COP 3.2 - Compliance date: January 1, 2010
All Other Types of Heating - EER 10.4 - COP 3.2 - Compliance date: January 1, 2010
=240,000 Btu/h and <760,000 Btu/h
No Heating or Electric Resistance Heating - EER 9.5 - COP 3.2 - Compliance date: January 1, 2010
All Other Types of Heating - EER 9.3 - COP 3.2 - Compliance date: January 1, 2010
VRF Multi-Split Heat Pumps (Water-Source)
<17,000 Btu/h
Without heat recovery
EER 12.0 - Compliance date: October 29, 2012
COP 4.2 - Compliance date: October 29, 2003
With heat recovery
EER 11.8 - Compliance date: October 29, 2012
COP 4.2 - Compliance date: October 29, 2003
=17,000 Btu/h and <65,000 Btu/h
EER 12.0 - Compliance date: October 29, 2003
COP 4.2 - Compliance date: October 29, 2003
=65,000 Btu/h and <135,000 Btu/h
EER 12.0 - Compliance date: October 29, 2003
COP 4.2 - Compliance date: October 29, 2003
=135,000 Btu/h and <760,000 Btu/h
Without heat recovery
EER 10.0 - Compliance date: October 29, 2013
COP 3.9 - Compliance date: October 29, 2013
With heat recovery
EER 9.8 - Compliance date: October 29, 2013
COP 3.9 - Compliance date: October 29, 2013